Technical data
• Standard: DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
• Temperature range (flexible): -15°C to +80°C
• Temperature range (fixed): -40°C to +80°C
• Nominal voltage: AC U0/U 300/500 V
• Test voltage core/core: 4000 V
• Breakdown voltage: 8000 V
• Mutual capacitance core/core: at 800 Hz (0.5–2.5 mm²): approx. 150 pF/m
• Mutual capacitance core/screen: at 800 Hz (0.5–2.5 mm²): approx. 270 pF/m
• Coupling resistance: at 30 MHz: approx. 250 Ohm/km
• Minimum bending radius (flexible): 10x Outer-Ø
• Minimum bending radius (fixed): 5x Outer-Ø
Cable structure
• Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
• Core insulation: PVC, compound type Z 7225
• Core identification acc. to DIN VDE 0293-334, black cores with consecutive labeling in white digits
• Protective conductor: starting with 3 cores (G = with GN-YE in the outer layer; x = without protective conductor (OZ))
• Cores stranded in layers with optimal lay lengths
• Inner sheath: PVC
• Screen: braided screen of tinned copper wires, approx. coverage 85%
• Outer sheath: PVC
• Sheath colour: transparent
• Length marking: in metres
Properties
• largely resistant to: oil (for details, see ‘Technical Information’)
• materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
• flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
• certifications and approvals: EAC; VDE-Reg.-No. 7032 (valid for temperature range up to +70°C)
Application
PVC control and connection cable for measurement and control technology, machine and machine tool construction, conveyers and production lines, computers and signal cable applications in electronics; high screening density supports interference-free transmission of signals/pulses. Not suitable for outdoor use.
Notes
• the conductor is metrically (mm²) constructed, AWG numbers are approximated and are for reference only
Legal notice: Images and technical data are sourced from official Helukabel documents. All rights remain with HELUKABEL® GmbH. Specifications may change without notice and errors cannot be fully excluded.



Reviews
There are no reviews yet.