Manufacturer: Helukabel
Technical Data
- PVC control cable acc. to UL-Std. 758 (AWM) Style 2587, CSA-Std. C22.2 No. 210 – AWM I/II A/B,
- 2 – 50 core(s): acc. to DIN VDE 0285-525-2-51 / DIN EN 50525-2-51;
- 61 core(s): in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
- Temperature range HAR flexible -5°C to +70°C
- HAR fixed -40°C to +70°C
- UL (AWM) flexible -5°C to +90°C
- UL (AWM) fixed -40°C to +90°C
- Nominal voltage HAR AC U0/U 300/500 V
- UL (AWM) AC 600 V
- Test voltage core/core 3000 V
- Breakdown voltage 6000 V
- Minimum bending radius flexible 7.5x Outer-Ø
- fixed 4x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2), UL-Std. 1581
- Core identification acc. to DIN VDE 0293-334, black cores with consecutive labeling in white digits
- Protective conductor: starting with 3 cores
- G = with protective conductor GN-YE, in the outer layer (JZ)
- x = without protective conductor (OZ)
- Cores stranded in layers with optimal lay lengths
- Outer sheath: oil-resistant special PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM5), UL-Std. 1581
- Sheath colour: grey (RAL 7001)
- Length marking: in metres
Properties
- resistant to: oil
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2, UL-VW-1, CSA FT1
- oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404, UL-Std. 1581 Tab. 50.182
- certifications and approvals: HAR, EAC
Application
- Multi-standard control cable especially for use in export-oriented machine and plant construction;
- for flexible application with medium mechanical stress and free movement without tensile stress and without forced movement guidance in dry, damp and wet rooms, but not outdoors.
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Legal notice: Images and technical data are sourced from official Helukabel documents. All rights remain with HELUKABEL® GmbH. Specifications may change without notice; despite careful preparation, errors cannot be fully excluded.