Technical Data
- Standards: DIN VDE 0285-525-2-51 / DIN EN 50525-2-51; DIN VDE 0285-525-3-11 / DIN EN 50525-3-11
- Temperature (flexible): -25°C to +70°C
- Temperature (fixed): -40°C to +70°C
- Nominal voltage: AC U0/U 300/500 V
- Test voltage core/core: 4000 V
- Min. bending radius (flexible): 12.5× Outer Ø
- Min. bending radius (fixed): 4× Outer Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: halogen-free polymer acc. to DIN VDE 0207-363-7 / DIN EN 50363-7 (compound type TI6)
- Core identification acc. to DIN VDE 0293-334, black cores with consecutive labeling in white digits
- Protective conductor: starting with 3 cores; G = with protective conductor GN-YE (JZ), x = without protective conductor (OZ)
- Cores stranded in layers with optimal lay lengths
- Outer sheath: halogen-free polymer acc. to DIN VDE 0207-363-8 / DIN EN 50363-8 (compound type TM7)
- Sheath colour: grey (RAL 7001)
- Length marking: in metres
Properties
- Largely resistant to oil
- Halogen-free
- Cadmium-free, contains no silicone, free from substances harmful to the wetting properties of lacquers
- Highly flame-retardant
Tests
- Halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
- Corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
- Flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- Bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
- Smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
- Certifications/approvals: EAC
Notes
- Conductor is metrically (mm²) constructed; AWG numbers are approximated and for reference only
- Please note “cleanroom qualification” in your order
Application
Control and connection cable in tool machinery, conveyor belts, production lines, plant construction, in air-conditioning devices, in metallurgical, steel and rolling mills. For fixed installation and flexible applications with occasional, not constantly recurring free movement without forced motion, without tensile stress and for medium mechanical stress. Suitable for use in dry, damp and wet locations and on plaster.
Legal notice: Images and technical data are sourced from official Helukabel documents. HELUKABEL® GmbH remains the owner of all trademarks and materials. Specifications may change without notice; despite careful preparation, errors cannot be fully excluded.



Reviews
There are no reviews yet.