Manufacturer: Helukabel
Technical Data
- Rubber connection cable, H07RN-F acc. to DIN VDE 0285-525-2-21 / DIN EN 50525-2-21; 07RN-F in alignment with DIN VDE 0285-525-2-21 / DIN EN 50525-2-21
- Temperature range flexible -25°C to +60°C
- fixed -30°C to +60°C
- Permissible operating temperature of the conductor +60°C
- Nominal voltage AC U0/U 450/750 V
- Max. permissible operating voltage alternating current (AC) conductor/earth 476 V
- three-phase alternating current (AC) conductor/conductor 825 V
- direct current (DC) conductor/earth 619 V
- direct current (DC) conductor/conductor 1238 V
- Test voltage core/core 2500 V
- Tensile stress during installation and operation 15 N/mm²
- Minimum bending radius fixed 4x Outer-Ø
- flexible, guidance via roles 7.5x Outer-Ø
- flexible, winding on drums 5x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: rubber acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI4)
- Core identification acc. to DIN VDE 0293-308
- 1 core(s): black
- 2 – 5 core(s): colour coded
- 7 – 37 core(s): black cores with consecutive labeling in white digits
- Protective conductor: starting with 3 cores
- G = with protective conductor GN-YE, in the outer layer
- x = without protective conductor
- Cores stranded in layers with optimal lay lengths
- Outer sheath: rubber acc. to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (compound type EM2)
- Sheath colour: black
Properties
- Resistant to: oil, weathering effects
- For outdoor use
Tests
- Flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- Oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404
- Certifications and approvals: H07RN-F: HAR; EAC
Notes
- The conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- Heavy duty, rubber sheathed cable for use with medium mechanical stress in dry, damp, wet rooms, in agricultural premises and outdoors.
- Suitable for equipment in commercial operations, e.g. heating plates, hand lamps, electric tools such as drills or circular saws.
- For fixed installation on plaster as well as in temporary constructions.
- When installed in pipes or similar enclosed systems, the use of the cable is permitted up to and including 1000 V AC voltage or up to 750 V DC voltage against earth.
Legal notice: Images and technical data are sourced from official Helukabel documents. All rights remain with HELUKABEL® GmbH. Specifications may change without notice; despite careful preparation, errors cannot be fully excluded.



Reviews
There are no reviews yet.